Replacement unit for the Cold Shot EZ Chiller Series

EZ Chiller Series

Cold Shot's starter chiller: 2, 3 and 5 tons, single-stage and air-cooled, for 44 to 70°F leaving fluid, indoors only.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Air-Cooled Portable 2 to 5 Tons 3

Specifications


Configuration & Size

Capacity:
2 to 5 tons at 50°F
Models:
3 part numbers
Leaving Fluid:
44 to 70°F
Process Pump:
1 hp, 30 GPM
Refrigerant:
R-410A

Construction

  • Hermetic scroll compressor, R-410A
  • Copper-aluminum or microchannel coil
  • Stainless copper-brazed evaporator
  • 25-gallon tank, 1 hp pump
  • PVC fluid connections

Ratings

  • Rated at 50°F leaving fluid
  • 95°F ambient, ±5%
  • Refrigerant R-410A
  • 208-230 V, one or three-phase

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

EZ Chiller Series, 2 to 5 Tons

A Starter Chiller, Fully Specified

Three models, one cabinet. The EZWC-24-B, EZWC-36-B and EZWC-60-B share a 72 x 47 x 34-inch cabinet, a 25-gallon tank and a 1 hp pump rated 30 GPM at 30 PSI, with 1-inch PVC MNPT connections.

Capacity is published at 50°F leaving fluid and 95°F ambient, ±5%: 24,000, 36,000 and 60,000 Btu/h, on a hermetic scroll compressor and R-410A, with a stainless steel copper-brazed evaporator.

The EZ page gives the electrical figures. The 2-ton runs on 208-230 V single-phase at 21.3 A MCA and a 30 A MOCP; the 3-ton on 208-230 V three-phase at 21.2 A and 30 A; the 5-ton at 24.7 A and 40 A.

It has limits, and says so. Cold Shot rates the EZ Chiller for indoor use only and for 44 to 70°F leaving fluid, a closed-loop, single-stage unit for small to medium operations.



injection molding machine with glowing molten material in a factory

Scroll compressor, 25-gallon tank and a 1 hp pump in one indoor cabinet, 2 to 5 tons.

Request a Quote

EZ Chiller Series Applications

Small brewery cellars
Small brewery cellars
Small molding presses
Small molding presses
Small finishing lines
Small finishing lines
Hydroponic reservoirs
Hydroponic reservoirs

schematic of the EZ Chiller series circuit, showing where the process fluid and the condenser heat go

Check the Temperature Before the Tons

The EZ Chiller's published range is 44 to 70°F leaving fluid. That covers mold cooling, most finishing baths and many water loops, but not a brewery crash to 30°F or a glycol loop below 40°F. If the process needs colder fluid, the EZ is the wrong starting point regardless of tonnage. The leaving fluid temperature guide explains what colder set points cost in capacity.

It is also indoor-only, so its condenser heat, about the cooling load plus compressor work, stays in the room. A 5-ton unit in a small space adds noticeable heat on a summer day.

Every part-number page below names the Temptek air-cooled portable we supply in its place, sized to cover the published 50°F capacity.
Call and talk it through with an engineer: 1-805-484-2992

EZ Chiller: Limits to Check Before Sizing

Because the 30 GPM pump is large for the load: at full rating the rise is about 1.6°F on the 2-ton EZWC-24-B, 2.4°F on the 3-ton and 4°F on the 5-ton, on water. Each figure is the Btu/h rating divided by 500 x 30. The narrow rise matters because many small loops are built around it: a press or a hydroponic reservoir sees nearly the same temperature in and out. If the process was designed for a larger rise, less flow would do. If hoses or long runs cut the flow well below 30 GPM, the rise grows and the far end of the loop runs warmer. Send the flow you measure, not only the pump label.

As a band: the 2-ton EZWC-24-B is published at 24,000 Btu/h ±5%, so a given unit may deliver anywhere from about 22,800 to 25,200 Btu/h at 50°F and 95°F ambient. The Temptek CG-2A we supply in its place is rated 2 tons, 24,000 Btu/h, which matches the nominal figure with no headroom. That is fine for a load that never reached the old unit's limit. If the existing EZ ran flat out on a summer afternoon and only just held set point, the load may sit at the top of the band, and we would look at the next size up. A quick check settles it: read the flow and the rise across the old unit on a hot afternoon. If 30 GPM is coming back 1.6°F warm, the load is the full 24,000 Btu/h, and the 2-ton pick has nothing to spare; if the rise is nearer 1°F, the load is closer to 15,000 Btu/h and the match is comfortable.

About 44 percent more capacity at 50°F: the CGD-7.5A is rated 86,400 Btu/h against the 60,000 Btu/h of the EZWC-60-B. The 3-ton EZWC-36-B gains about 33 percent on its move to the 4-ton CG-4A, 48,000 against 36,000 Btu/h. With the same 50°F leaving-fluid rating on both sides, that is straight margin. Check the space and the circuit, since a larger unit may need more of both.

They describe the existing circuit, not the new one: minimum circuit ampacity sets the wire size, and maximum overcurrent protection sets the largest breaker allowed. The replacement brings its own nameplate figures, and those decide whether the old wire and breaker can stay. The case that catches people is the 2-ton EZWC-24-B, the only single-phase EZ, so a three-phase replacement needs a new feed. On the 5-ton, the 40 A breaker is the ceiling for that unit only; a larger Temptek unit is checked against its own data, not against the old breaker. Tell us what the panel offers before the order.

Because the EZ is an indoor unit that puts its condenser heat into the room, and a larger replacement in the same spot puts in more. At full load the 5-ton EZWC-60-B moves 60,000 Btu/h out of the loop, and the room receives that plus the compressor work, through a single fan at 2300 CFM. A small cellar or press room that already runs warm in summer then climbs further, and an air-cooled chiller loses capacity as its intake air warms. The set point compounds it: a unit running near the 44°F floor of the EZ range has less in hand than one at 60°F. Tell us the room size, how it is ventilated and the set point, and we check the Temptek pick against the real air temperature.


EZ Chiller Units