Replacement unit for the Cold Shot WCWC Reverse Flow Series

WCWC Reverse Flow Series

Water-cooled chillers for open-loop processes: pump on board, no tank, fed by gravity from a trough, 1.5 to 100 tons.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Open-Loop Water-Cooled 1.5 to 100 Tons 21

Specifications


Configuration & Size

Capacity:
1.5 to 100 tons at 50°F
Models:
21 part numbers
Style:
Reverse flow
Process Pump:
1 to 7-1/2 hp
Refrigerant:
R-410A

Construction

  • Scroll compressors, R-410A
  • Water-cooled condenser
  • Stainless centrifugal pump
  • No tank: fed from a trough
  • Liquid receiver, head pressure control

Ratings

  • Rated at 50°F leaving fluid
  • 85°F condenser water
  • Refrigerant R-410A
  • Open-loop, gravity-fed pump

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

WCWC Reverse Flow Water-Cooled Chillers, 1.5 to 100 Tons

Open Loop, Water-Cooled

Twenty-one models with the RF suffix. Reverse flow units carry a pump and no holding tank. An external reservoir or trough feeds the pump by gravity, and the pump sends the fluid through the chiller and filter and back to the process or the tank.

Capacity is published at 50°F leaving fluid, on 85°F condenser water for the smaller units, from 18,000 Btu/h on the WCWC-18-E-RF to 1,200,000 Btu/h on the WCWC-1200-GC-RF. The GC reverse flow rows carry a "***" footnote the page does not define; each affected page carries the note.

The 40-ton unit is described in detail. Cold Shot's 40-ton page describes the WCWC-480-E-RF as a compact unit with PLC controls, self-diagnostics and WiFi, LAN or LTE connectivity, on R-410A, with VFD options for pressure or flow.

Pumps match the portables. From 1 hp at 30 GPM on the smallest to 7-1/2 hp at 300 GPM and 35 PSI on the WCWC-1200-GC-RF.



bright cleanroom corridor lined with white semiconductor tools

A water-cooled chiller and pump between an open trough and the process, with no tank of its own.

Request a Quote

WCWC Reverse Flow Series Applications

Plating and rinse tanks
Plating and rinse tanks
Cutting and grinding coolant
Cutting and grinding coolant
Tower-water plants
Tower-water plants
Trough and sump loops
Trough and sump loops

schematic of the WCWC Reverse Flow series circuit, showing where the process fluid and the condenser heat go

Suction Head Comes First

On an open loop the chiller's pump is only as good as what reaches its inlet. The external tank has to sit high enough, and the suction line has to be short and large enough, that the pump never runs short of fluid; a strainer that fills with debris from an open bath starves it the same way. These are the first things to look at when a reverse flow unit loses flow.

A water-cooled reverse flow unit adds the condenser water loop on top: tower or plant water at roughly 3 GPM per ton, treated to keep scale out. The indoor vs outdoor installation guide compares it with an air-cooled unit for the same job.

Every part-number page below names the Temptek unit we supply in its place, sized to cover the published 50°F capacity: a Temptek CG water-cooled portable to 40 tons and a TTI water-cooled central chiller from 50 tons. Both carry their own tank, so we set up the piping around the open loop.
Call and talk it through with an engineer: 1-805-484-2992

WCWC Reverse Flow in Practice: Suction and Piping

They mean the plant may rely on the chiller for more than cooling. Cold Shot describes the 40-ton unit with a PLC, remote connectivity and VFD options for pressure or flow. If alarms reach a phone, or the pump speed holds a header pressure on the open loop, tell us, and we specify the Temptek controls and pump arrangement around it, saying plainly where anything differs.

Its 7-1/2 hp pump moves 300 GPM at 35 PSI, and at its full rating the loop sees about an 8°F rise on water, 1.2 million Btu/h divided by 500 x 300. On a reverse flow unit, that 35 PSI is all there is for the chiller, the filter, the supply line and the run back to the trough, since the trough sits open to the atmosphere. A long run to a distant plating line uses it up quickly. The GC reverse flow rows also carry the undefined triple-asterisk footnote and omit the 85°F condenser water figure, so we size on the 50°F leaving fluid basis and confirm the condenser side with you.

With a Temptek CG water-cooled portable up to 40 tons, and from 50 tons a TTI central chiller on tower water, piped so the open trough and the chiller's own tank work together. The largest portable, the CG-40W, stops at 40 tons, which sets that break. There are two usual layouts. In the first, the trough return drains to the chiller's tank and the chiller's pump feeds the process; this suits a trough that sits above the chiller and carries little debris. In the second, the trough stays as the process reservoir and the chiller loop runs to and from it, which leaves the process pumping as it is but adds a second pump duty. Either way the bath passes through the chiller, so the trough elevation and what the bath carries decide the layout and the strainer. The condenser side stays in principle, at roughly 3 GPM per ton of treated tower water, and we confirm the connection sizes against the existing tower piping.