Replacement unit for the Cold Shot ACWC Portable Air-Cooled Series

ACWC Portable Air-Cooled Series

Cold Shot's air-cooled portable: compressor, condenser, tank and pump in one footprint, 1.5 to 90 tons, on a single power connection.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Air-Cooled Portable 1.5 to 90 Tons 27

Specifications


Configuration & Size

Capacity:
1.5 to 90 tons at 50°F
Models:
27 part numbers
Frames:
Q, E and GC
Process Pump:
1 to 7-1/2 hp
Refrigerant:
R-410A

Construction

  • Scroll compressors, R-410A
  • Air-cooled condenser, microchannel coil
  • Stainless brazed plate evaporator
  • Stainless centrifugal process pump
  • Insulated tank, bypass valve

Ratings

  • Rated at 50°F leaving fluid
  • 95°F ambient air
  • Refrigerant R-410A
  • 208-230 V single-phase to 5 tons

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

ACWC Portable Air-Cooled Chillers, 1.5 to 90 Tons

The Whole Chiller in One Footprint

Twenty-seven models across three frames. The Q frame runs 1.5 to 10 tons, the E frame 12.5 to 40 tons and 70 tons, and the GC frame 25 to 90 tons. DM models list two pump ratings, and DP models are the dual-pump builds Cold Shot lists from 50 tons up.

Capacity is published at 50°F leaving fluid and 95°F ambient, from 18,000 Btu/h on the ACWC-18-Q to 1,080,000 Btu/h on the ACWC-1080-GC-DP. Cold Shot's per-size pages describe the 40-ton portable as a two-stage unit on dual hermetic scroll compressors and R-410A.

The pump grows with the frame. A 1 hp stainless centrifugal pump rated 30 GPM at 30 PSI to 5 tons, 1-1/2 hp at 55 GPM to 10 tons, 2 and 3 hp on the E frame, and 7-1/2 hp at 160 to 225 GPM on the GC units. Connections run from 3/4-inch MNPT to 4-inch flanges.

Single-phase stops at 5 tons. The 1.5 and 2-ton units are listed on 208-230 V single-phase only, the 3 and 5-ton units on single or three-phase, and everything from 7.5 tons up on three-phase.



frost-covered process pipes in winter

Scroll compressors, air-cooled condenser, insulated tank and stainless pump, with one electrical connection.

Request a Quote

ACWC Portable Air-Cooled Series Applications

Plastics molding
Plastics molding
Metal finishing
Metal finishing
Machine tools
Machine tools
Brewery glycol
Brewery glycol

schematic of the ACWC Portable Air-Cooled series circuit, showing where the process fluid and the condenser heat go

Portable Means Self-Contained

Cold Shot is explicit that "portable" describes the configuration, not the mobility: most of these units are never moved once installed. What it means is that the refrigeration circuit, the reservoir and the pump share one footprint and one power connection, and the loop is closed: all the fluid the pump sends out comes back to the tank under the pump's own pressure.

An air-cooled portable also puts its condenser heat into the room, roughly the cooling load plus the compressor work. A 40-ton unit indoors adds well over half a million Btu/h to the building, which is fine in winter and a problem in August. The indoor vs outdoor installation guide covers when the chiller belongs outside.

Every part-number page below names the Temptek unit we supply in its place, sized to cover the published 50°F capacity: a Temptek CG air-cooled portable to 25 tons, and a Temptek TTI air-cooled central chiller from 30 tons, where the largest Temptek portable falls short.
Call and talk it through with an engineer: 1-805-484-2992

ACWC Portables: Model Codes and Set Points

Usually: on most models it is the capacity in thousands of Btu/h at 50°F, so the ACWC-240-E is 240,000 Btu/h, or 20 tons, and the ACWC-1080-GC-DP is 90 tons. Where a model departs from that, go by the figure on its part-number page, not the code. When a replacement is quoted from a code typed into an old purchase order, a dropped suffix is the usual slip, so read the nameplate. The DP suffix in particular tells us the loop was built around two pumps, and DM tells us the unit lists two pump ratings, so the pump to match has to be confirmed.

On paper they share the same 40-ton rating, 480,000 Btu/h, but they come from two different Cold Shot pages with two different voltage listings, so treat them as separate part numbers. The ACWC-480-E sits on the 40-ton page, which describes it as two-stage, with two hermetic scroll compressors; the ACWC-480-GC sits on the Chiller Specifications page. Two stages matter at part load, where one compressor can carry a light load instead of a single large one cycling on and off. For the replacement, the frame letter and the voltage on the nameplate decide which listing applies. The capacity basis is the same, so the published difference is in the electrical data, not the tonnage.

Cold Shot's tables publish no set point range for the ACWC portables; they give capacity at a single point, 50°F leaving fluid with 95°F air, and nothing more. That leaves two practical points. Above 50°F capacity rises, so a molding loop at 60°F has more in hand than the table shows. Below 50°F it falls, and the colder the set point, the more glycol the loop needs to protect the evaporator. A brewery glycol loop is where this bites: an ACWC picked from its 50°F row for a loop that runs much colder can come up well short on the first crash. Give us the set point you run, and the Temptek unit is sized at it.

Because no Temptek portable covers 30 tons, so the 30-ton ACWC-360-E goes to the TTI-40A central chiller at 40 tons, about 33 percent above it. One size down, the CG-30A portable, rated 29 tons at 50°F, covers the 25-ton ACWC-300-E with about 16 percent to spare. That step buys room for a colder set point or added load. Send the floor space with the request, since the TTI is a diffrent package.