Replacement unit for the ICS Cool Energy i-Chiller Compact Series

i-Chiller Compact Series

ICS's smallest i-Chiller: a compact 230 V unit with a 15 or 22-liter tank, 1.72 to 4.53 kW nominal.

PRODUCT TYPE CAPACITY MODELS
Compact Chiller Compact, Air-Cooled 1.7 to 4.5 kW 4

Specifications


Configuration & Size

Capacity:
1.72 to 4.53 kW nominal
Models:
4 part numbers
Supply:
230 V, 1 ph, 50/60 Hz
Tank:
15 or 22 liters
Fluid Range:
to -5 or 0 / +30°C

Construction

  • Compact air-cooled cabinet
  • 15 or 22-liter storage tank
  • 1/2-inch BSP connections
  • 230 V single-phase, 50/60 Hz
  • Fluid supply 0 or -5 to +30°C

Ratings

  • Nominal kW, 50 Hz
  • Ambient +5 to +45°C
  • SEPR HT 4.51 to 4.86
  • Rating point not stated

Specifications sourced from ICS Cool Energy's published i-Chiller product pages and datasheets (icscoolenergy.com), October 2026. ICS Cool Energy and i-Chiller are trademarks of their owner; referenced here for cross-reference only. Capacities are ICS's nominal figures in kW, converted at 3.517 kW per ton. Confirm against the unit nameplate before ordering.

i-Chiller Compact, 1.7 to 4.5 kW

Small and Single-Phase

Four models. The iC03C, iC05C, iC08C and iC10C, from 1.72 to 4.53 kW nominal; the iC03C also lists 1.92 kW at 60 Hz.

Single-phase power. All four run on 230 V single-phase, 50 or 60 Hz, in a 660 x 486 mm cabinet, 623 or 876 mm tall.

A tank on board. 15 liters on the iC03C and iC05C, 22 on the iC08C and iC10C, with 1/2-inch BSP water connections.

Wide limits. Ambient +5 to +45°C, and fluid supply from 0°C (iC03C, iC05C) or -5°C (iC08C, iC10C) up to +30°C.



coils of stainless steel sheet in a warehouse

Compressor, condenser, a small tank and controls in one compact 230 V cabinet.

Request a Quote

i-Chiller Compact Series Applications

Lasers
Lasers
Lab instruments
Lab instruments
Small molding
Small molding
Small loops
Small loops

schematic of the i-Chiller Compact series circuit, showing where the process fluid and the condenser heat go

From kW to Tons

A kW of cooling is 0.284 tons; the iC05C's 2.64 kW is about 0.75 tons. ICS does not state the rating point for the Compact on its product page, so the pick is sized on Temptek's 0.80 multiplier to be safe. The glycol chiller sizing guide works the load from flow and temperture rise.

Every part-number page below names the Temptek unit we supply in its place, sized from ICS's nominal kW on Temptek's 0.80 multiplier at 40°F, which covers a 12/7°C rating, and built for North American supply rather than 400 V / 50 Hz.
Call and talk it through with an engineer: 1-805-484-2992

ICS i-Chiller Compact: kW, Tons and Supply

Size from 1.92 kW if the iC03C has been running on a 60 Hz supply, because that is the capacity the process has actually been getting. At 1.92 kW the unit makes about 0.55 tons, and the 0.80 multiplier then asks for 0.68 tons of Temptek rating at 50°F. Working from the 50 Hz figure instead gives 0.49 tons and a call of 0.61, roughly ten percent short of what the loop is used to. The other three models list only a 50 Hz number, so for those the nameplate and the supply frequency settle which figure applies.

Because the iC10C's 4.53 kW, about 1.29 tons, works out to 1.61 tons after dividing by 0.80, which is more than the 1.5 tons the CF-1.5A carries at 50°F. The iC08C, at 0.97 tons, needs only 1.21 tons, so the CF-1.5A covers it with 0.29 tons to spare. The two models share the taller cabinet, the 22-liter tank and the -5°C fluid limit, so it is easy to assume they share a replacement as well. They do not, and the iC10C's own part-number page carries its pick. If your iC10C has never run near full load, send the measured load too, and the selection can be checked against it.

Only if the model quoted is a single-phase build, so confirm the phase as well as the voltage before ordering. Every Compact runs on 230 V single-phase at 50 or 60 Hz, often from a lab or bench circuit, and the Temptek units we supply are built for North American 460 V / 60 Hz or 230 V. A 230 V three-phase unit will not start on that circuit. Size the breaker and wiring from the new nameplate, not the old one.

It has to be reworked at the real set point, because the 0.80 multiplier is taken at 40°F to cover ICS's nominal rating, not a set point below freezing. The iC08C and iC10C are listed down to -5°C, which is 23°F, and the iC03C and iC05C to 0°C, or 32°F. Any chiller makes noticeably less at those temperatures than at its nominal point, so a pick taken straight from the nominal kW would run short. The loop also needs glycol at a strength that suits the colder set point. Send the set point and the mix, and the unit is selected at that temperature instead of at 40°F.