1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the ICS Cool Energy i-Chiller Compact n Series

i-Chiller Compact n Series

ICS's natural-refrigerant compact: the Compact n on R290 propane, 1.19 to 2.98 kW at 12/7°C and 35°C ambient.

PRODUCT TYPE CAPACITY MODELS
Compact Chiller Compact, R290 1.2 to 3.0 kW 4

Specifications


Configuration & Size

Capacity:
1.19 to 2.98 kW nominal
Models:
4 part numbers
Refrigerant:
R290 propane
Tank:
15 or 22 liters
Supply:
230 V, 1 ph, 50 Hz

Construction

  • R290 propane refrigerant
  • 15 or 22-liter storage tank
  • Optional P3 or P5 pump
  • 230 V single-phase
  • 0 to +30°C outlet

Ratings

  • EN 14511, 12/7°C water
  • 35°C ambient
  • Ambient +5 to +45°C
  • Sound pressure 46-47 dB(A)

Specifications sourced from ICS Cool Energy's published i-Chiller product pages and datasheets (icscoolenergy.com), October 2026. ICS Cool Energy and i-Chiller are trademarks of their owner; referenced here for cross-reference only. Capacities are ICS's nominal figures in kW, converted at 3.517 kW per ton. Confirm against the unit nameplate before ordering.

i-Chiller Compact n, 1.2 to 3.0 kW

Propane in a Small Package

Four models. The IC03n, IC05n, IC08n and IC10n, from 1.19 to 2.98 kW at 12/7°C water and 35°C ambient under EN 14511.

A second rating. The datasheet also lists 1.71 to 4.37 kW at 20/15°C water and 25°C ambient.

Quiet. Sound pressure of 46 to 47 dB(A), with a 15 or 22-liter tank and 1/2-inch Rp connections.

Pumps are options. ICS offers a peripheral P3 pump (3 bar) or P5 pump (5 bar); weights rise by about 5 to 6 kg with the P3.



chemical dosing pumps and totes in a plant

R290 compressor, condenser and a small tank, with an optional peripheral pump, on 230 V.

Request a Quote

i-Chiller Compact n Series Applications

Lab instruments
Lab instruments
Lasers
Lasers
Low-GWP duty
Low-GWP duty
Small loops
Small loops

schematic of the i-Chiller Compact n series circuit, showing where the process fluid and the condenser heat go

The One ICS Line With a Stated Rating

Of the i-Chiller tables, only the Compact n datasheet states its rating point: 12/7°C water at 35°C ambient. 7°C is 44.6°F, so the pick is sized on Temptek's 0.80 multiplier at 40°F, which covers it.

Every part-number page below names the Temptek unit we supply in its place, sized from ICS's nominal kW on Temptek's 0.80 multiplier at 40°F, which covers a 12/7°C rating, and built for North American supply rather than 400 V / 50 Hz.
Call and talk it through with an engineer: 1-805-484-2992

R290 Compact n: Rating and Replacement Notes

About 30 percent: the 12/7°C, 35°C-ambient figures come to 68 to 70 percent of the 20/15°C, 25°C-ambient ones. At the small end of the range 1.71 kW becomes 1.19 kW, and at the large end 4.37 kW becomes 2.98 kW. That gap is what eight degrees Celsius of water and ten of ambient do to one small machine, and it is why the warmer figure should never be set beside a Temptek rating. If your process runs at 15°C or warmer, the replacement has more in hand than the 12/7°C sizing suggests.

Because its 0.85 tons becomes 1.06 tons once divided by the 0.80 multiplier, which takes it past the CF-1A used for the IC08n. The IC08n's 0.63 tons calls for about 0.79 tons, and the IC03n's 0.34 tons for 0.43, inside the CF-.5A's 0.5 tons at 50°F. The multiplier is applied because the Compact n is rated at 7°C (44.6°F) water while the Temptek pick is taken at 40°F, the colder and safer side of that point. The selection is made on capacity alone. The R290 charge stays with the ICS unit, so if a natural refrigerant is written into a site or customer requirement, raise it before the model is fixed.

It can starve the instrument of flow, because a P5 unit was chosen to push 5 bar, and a loop built around that pressure will not get its flow from a 3-bar pump. The symptom is a flow alarm on the laser or analyzer, or a fluid temperature rise across it larger than its maker allows, while the chiller itself reports no fault. Find out which pump the unit carries before it goes. The option is on the ICS order, and weight shows whether a pump is fitted at all: the IC03n is 63 kg bare and 68 kg with the P3. Then give us the flow and pressure the instrument needs, along with the hose run, so the pump on the replacement is chosen for that loop instead of assumed.


i-Chiller Compact n Units


Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales