Replacement unit for the ICS Cool Energy i-Chiller Process e Series

i-Chiller Process e Series

ICS's low-GWP process chiller: the i-Chiller Process e on R513A or R454B, 4.96 to 190.26 kW nominal, with a tank on board.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Packaged, Low-GWP 5.0 to 190.3 kW 21

Specifications


Configuration & Size

Capacity:
4.96 to 190.26 kW nominal
Models:
21 part numbers
Refrigerant:
R513A or R454B
Tank:
60 to 950 liters
Max Ambient:
46°C

Construction

  • Packaged air-cooled
  • 60 to 950-liter storage tank
  • One or two compressors
  • Max ambient 46°C
  • 400 V three-phase

Ratings

  • Nominal kW
  • EER 2.44 to 3.02
  • R513A (A) or R454B (G)
  • Rating point not stated

Specifications sourced from ICS Cool Energy's published i-Chiller product pages and datasheets (icscoolenergy.com), October 2026. ICS Cool Energy and i-Chiller are trademarks of their owner; referenced here for cross-reference only. Capacities are ICS's nominal figures in kW, converted at 3.517 kW per ton. Confirm against the unit nameplate before ordering.

i-Chiller Process e, 5 to 190 kW

The Refrigerant Is in the Name

Twenty-one models. From the iC220A at 4.96 kW to the iC7100G at 190.26 kW nominal; A models run on R513A and G models on R454B.

One or two compressors. One compressor to the iC416G, two on one circuit from the iC520G up.

Tanks from 60 to 950 liters. And frames from 560 to 1,250 mm wide, 199 to 2,936 kg working weight.

Hot climates. ICS lists a maximum external air temperature of 46°C on every model.



backflow prevention valves on a water line

One or two compressors, condenser, evaporator and a storage tank, on R513A or R454B.

Request a Quote

i-Chiller Process e Series Applications

Plastics molding
Plastics molding
Low-GWP duty
Low-GWP duty
Process cooling
Process cooling
Outdoor pads
Outdoor pads

schematic of the i-Chiller Process e series circuit, showing where the process fluid and the condenser heat go

R454B Is an A2L Refrigerant

The G models use R454B, classed A2L, mildly flammable, with its own rules for the space the chiller sits in. The A models use R513A. Check which one the nameplate carries before planning the swap.

Every part-number page below names the Temptek unit we supply in its place, sized from ICS's nominal kW on Temptek's 0.80 multiplier at 40°F, which covers a 12/7°C rating, and built for North American supply rather than 400 V / 50 Hz.
Call and talk it through with an engineer: 1-805-484-2992

i-Chiller Process e: Refrigerant, Circuits, Ambient

Yes, because even the larger of the two fits under the TTOACS-80D-MZC-2P's 75.8 tons once the multiplier is applied. The iC7100G's 190.26 kW is about 54.10 tons and calls for 67.62 tons, leaving about 8.2 tons in hand; the iC790G, a smaller size, has more. On an iC790G running well under its rating, send the measured load, since a 75.8-ton unit on a light load spends most of its hours unloaded.

It gives staging but no refrigerant-side backup, because both compressors share one circuit. The iC525G, 47.66 kW or about 13.55 tons, is built that way, as is every size from the iC520G to the iC7100G. A leak, a high-pressure trip or a failed expansion valve on that circuit stops both compressors at once. If the process cannot tolerate a full stop, say so when the replacement is chosen, because redundancy then has to be designed in on purpose rather than read from the compressor count.

Only the small end stays portable. The iC220A's 4.96 kW, about 1.41 tons, needs 1.76 tons after the 0.80 multiplier and goes to the CG-2A. By the iC407A, the last of the R513A sizes, the pick is the outdoor TTOACS-7.5S-CG-1P at 7.8 tons, and the G models carry on in the same family: the iC412G to the TTOACS-15S-CG-1P and the iC640G to the TTOACS-40S-CG-1P at 38.4 tons. A Process e standing inside a plant today may therefore give way to a unit on a pad outside, so plan the wall penetration, the outdoor piping and its freeze protection with the order.

The real summer air temperature at the condenser inlet, measured, not taken from the weather report. ICS lists 46°C, about 115°F, as the top external air temperature, but it's nominal kW is not given at that condition, so the pick is confirmed at your ambient after the 0.80 sizing. The usual mistake is a unit placed where its own discharge air, or a neighbor's, loops back into the coil: the inlet then runs well above the yard temperature and capacity falls on the hottest afternoons. Tell us what stands within a few meters of the chiller, too.