Central Chiller Series

Mokon's indoor central chillers: 30 to 120 tons, single or dual circuit, for a separate pump tank, air-cooled through a remote condenser or water-cooled.

PRODUCT TYPE CAPACITY MODELS
Central Chiller Central, Indoor 30 to 120 Tons 26

Specifications


Configuration & Size

Capacity:
30 to 120 tons nominal
Models:
26 part numbers
Circuits:
Single or dual
Compressors:
30 to 4 x 30 hp
Pump and Tank:
Separate

Construction

  • Scroll compressors, staged
  • Single or dual circuit
  • Brazed plate evaporators
  • Electronic hot gas bypass
  • Carel controller, NEMA 12 panel

Ratings

  • Listed in nominal tons
  • No rating point published
  • Down to 20°F leaving fluid
  • Remote condenser or water-cooled

Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.

Central Chillers, 30 to 120 Tons

The Chiller Half of a Central System

Twenty-six part numbers. ASC and WSC are single-circuit, air-cooled and water-cooled, at 30 to 120 tons; ADC and WDC are dual-circuit at 30 and 50 to 120 tons.

Listed in nominal tons. Mokon's table gives the tons and compressor horsepower, from one 30 hp scroll on the ASC30 to four 30 hp scrolls on the 120-ton units, but no rating point, pump, tank or electrical data.

Air-cooled means a remote condenser. The ASC and ADC models use outdoor air-cooled condensers, and Mokon publishes the pairing, from the CNR-035 at 30 tons to the CNR-139 at 120.

Controls follow the circuits. A Carel Micro on single-circuit units and a Carel pCO with a color touch screen on dual-circuit ones, with compressor staging and electronic hot gas bypass, down to 20°F leaving fluid.



insulated distribution pipes running outdoors

Staged scroll compressors and brazed plate evaporators, piped to a separate pump tank and a remote condenser or tower.

Request a Quote

Central Chiller Series Applications

Pump-tank systems
Pump-tank systems
Plant-wide molding
Plant-wide molding
Tower water plants
Tower water plants
Central chilled water
Central chilled water

schematic of the Central Chiller series circuit, showing where the process fluid and the condenser heat go

Nominal Tons Need a Second Look

A nominal 60-ton chiller is a 60-ton chiller at the condition the maker had in mind, and Mokon does not say which condition that is. At 50°F leaving fluid on a mild day it may make more; at 20°F on glycol it makes much less. These pages match on the nominal figure and say so, and the size is confirmed against your set point, glycol and condenser conditions before we quote.

The tonnage and capacity guide and the leaving fluid temperature guide cover the arithmetic.

Every part-number page below names the Temptek unit we supply in it's place, a Temptek indoor chiller or chilling module with a remote condenser for the air-cooled models, and a water-cooled chilling module for the water-cooled ones, matched on the nominal tons.
Call and talk it through with an engineer: 1-805-484-2992

Mokon Central Chillers: Nominal Tons and Circuits

The voltage, phase and frequency, the minimum circuit ampacity and maximum fuse size, and the model code, because Mokon's table stops at tons and compressor horsepower. The model code tells us single or dual circuit and air or water-cooled, and the compressor line, a single 30 hp scroll at 30 tons up to 4 x 30 hp at 120, shows how the capacity is split. A photo of the plate on the remote condenser helps as well. With those, the Temptek module and its feed are sized together, and the panel work is known before the quote.

No, the circuit count is in the model letters, not the compressor count: the single-circuit ASC120 and the dual-circuit WDC120 both run 4 x 30 hp. S models, ASC and WSC, carry one circuit on a Carel Micro; D models, ADC and WDC, carry two on a Carel pCO. With four equal compressors either type stages in quarter steps, but only the dual-circuit unit can keep running on one circuit when a refrigerant fault takes the other down. Read the middle letter on the plate before deciding whether redundancy has to carry over.

Which CNR is on the roof, how long the refrigerant lines are and how much they rise, because the Temptek indoor chiller or module is selected with its own remote condenser. Mokon pairs the CNR-035 with 30 tons, the CNR-064 with 2x2 fans with 60, the CNR-115 with 2x3 fans with 100 and the CNR-139 with 2x4 fans with 120. Plan on a new condenser unless the quote says otherwise, and check that the roof steel or pad can take a different footprint. Line length and elevation between the indoor unit and the condenser shape the refrigerant piping as much as the tonnage does.

Yes, both water-cooled 80-ton models map to the MW-80-CC chilling module, because the match is made on nominal tons and Mokon publishes no rating point that would separate them. The same rule gives the ASC60 the MA-60-RC-C at 60 tons and the ADC100 the MA-105-RC-CCC at 103. A nominal-for-nominal match leaves little or no margin, so the check at your set point, glycol mix and condenser water temperature is what fixes the final size. If the WDC80's second circuit was there for redundancy, tell us, since that is a design question, not a tonnage one.