Replacement unit for the Mokon Iceman Micro Series

Iceman Micro Series

Mokon's smallest chiller: a tabletop Iceman Micro at 3,200 Btu/h, on 115 V, for labs, lasers and micro-molding.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Tabletop Portable 1/4 Ton 2

Specifications


Configuration & Size

Capacity:
3,200 Btu/h at 50°F
Models:
2 part numbers
Leaving Fluid:
20 to 60°F
Process Pump:
1/12 hp, up to 2.3 GPM
Refrigerant:
R-513A

Construction

  • Hermetic compressor, R-513A
  • Seal-less magnetic drive pump
  • Brazed plate evaporator
  • 4-gallon insulated plastic tank
  • Air-cooled or tube-in-tube water-cooled

Ratings

  • Rated at 50°F leaving fluid
  • 90°F ambient, 2.4 GPM/ton
  • 85°F condensing water
  • 20 to 60°F range

Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.

Iceman Micro Series, 1/4 Ton

A Chiller Sized for One Instrument

Two models, one size. The AF-1233 is air-cooled with a fin-and-tube condenser; the WF-1233 is water-cooled with a tube-in-tube condenser. Both are listed at 3,200 Btu/h at 50°F leaving fluid.

It plugs into the wall. Mokon lists the Micro on 115 V single-phase, 60 Hz, with a power cord, in a 26 x 17 x 28-inch cabinet that ships at about 150 lbs.

The pump is small and seal-less. A 1/12 hp magnetic drive plastic pump moves 0.8 to 2.3 GPM at up to 9 PSI, from a 4-gallon insulated tank with the level visible from outside.

The range is 20 to 60°F. Mokon rates it on R-513A and calls it ideal for laboratory applications, laser cooling and micro-molding.



flow meters mounted along a process line

Compressor, 4-gallon tank and a seal-less pump in a tabletop cabinet, on 115 V.

Request a Quote

Iceman Micro Series Applications

Lasers
Lasers
Lab instruments
Lab instruments
Micro-molding
Micro-molding
Small process loops
Small process loops

schematic of the Iceman Micro series circuit, showing where the process fluid and the condenser heat go

Match the Flow Before the Btu

At this size the instrument decides the chiller. A laser or analyzer usually states the flow, inlet pressure and temperature it needs, and a 1/12 hp pump at up to 9 PSI covers a short hose run, not a long one. Check those figures first; the 3,200 Btu/h is easy to match, a pressure drop is not.

Below 50°F the capacity falls; the leaving fluid temperature guide explains by how much.

Every part-number page below names the Temptek unit we supply in its place, a Temptek CF fractional-ton unit for the air-cooled model. Temptek's smallest water-cooled portable is 2 tons, so the WF-1233 page names it and notes that an air-cooled CF is the closer size.
Call and talk it through with an engineer: 1-805-484-2992

Iceman Micro: Flow, Pressure and Power

At the full 3,200 Btu/h, about 2.8°F at 2.3 GPM and about 8°F at 0.8 GPM, from Btu/h = 500 x GPM x delta-T on water. That is why the pump curve matters as much as the capacity: a laser that allows only a small rise across its head needs the upper end of the flow range, and a long or narrow hose run pushes the pump toward the lower end. Measure the rise across the instrument today and hold it the same with the replacement.

Not necessarily, so confirm the supply before ordering, since the Micro's cord-connected 115 V single-phase service is one of the reasons it suits a lab bench. Tell us what receptacles are available where the unit sits, and whether a dedicated circuit is possible. If only a standard 115 V outlet is on hand, that becomes a selection requirement on the quote, along with the bench space the Micro's cabinet takes now.

About 280 Btu/h, or 9 percent: the CF unit is rated 0.29 tons, roughly 3,480 Btu/h, at 50°F against the AF-1233's 3,200 Btu/h, about 0.27 tons. The CF figure is also taken at 95°F ambient, five degrees hotter than Mokon's 90°F, so the real cushion in a normal lab is a little larger. Both machines lose capacity below 50°F, so at a 30°F set point the comparison has to be made again at that temperature.

It runs far below its size, since the CG-2W at 2 tons is about seven and a half times the WF-1233's 3,200 Btu/h, and holds temperture by cycling or bypassing for nearly all of its hours. It also needs condenser water and floor space a Micro never did. The usual reason for a water-cooled Micro is a room that cannot take condenser heat. If that still applies, the CG-2W is the choice; if the room can absorb the small heat of a CF unit, the air-cooled CF is the closer size and the simpler install.