Replacement unit for the Mokon Outdoor Central Chiller Series

Outdoor Central Chiller Series

Mokon's outdoor central chillers: 356,000 to 1,491,000 Btu/h with a 100 to 750-gallon tank on board, for -20 to 95°F ambient.

PRODUCT TYPE CAPACITY MODELS
Central Chiller Central, Outdoor 30 to 124 Tons 14

Specifications


Configuration & Size

Capacity:
356,000 to 1,491,000 Btu/h
Models:
14 part numbers
Leaving Fluid:
20 to 65°F
Ambient:
-20 to 95°F
Tank:
100 to 750 gallons

Construction

  • Hermetic scroll compressors
  • Brazed plate evaporator
  • UV-protected Armaflex insulation
  • NEMA 4 local, NEMA 12 remote panel
  • Remote condenser from 60 tons

Ratings

  • Rated at 50°F leaving fluid
  • 90°F ambient, 2.4 GPM/ton
  • 85°F condensing water, 3 GPM/ton
  • Derate for pump selected

Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.

Outdoor Central Chillers, 30 to 120 Tons

A Central Plant on a Pad

Fourteen part numbers in seven pairs. OAC models are air-cooled and OWC water-cooled, from 356,000 Btu/h on the OAC-30 to 1,491,000 Btu/h on the OWC-120, at 50°F leaving fluid.

Rated before the pump. Mokon rates the air-cooled units at 90°F ambient and 2.4 GPM per ton and the water-cooled ones on 85°F condensing water at 3 GPM per ton, and says to derate for the pump horsepower selected, from 3 to 7-1/2 hp.

The tank grows fast. A 100-gallon tank at 30 and 40 tons, 150 at 50 and 60, 500 at 80 and 100, and 750 at 120, with 2-inch FNPT to 4-inch flanged connections.

Remote condensers from 60 tons. Mokon provides the air-cooled units from 60 tons up with a remote air-cooled condenser. All run 20 to 65°F leaving fluid in -20 to 95°F ambient.



polished stainless water piping along a cleanroom corridor

Scroll compressors, evaporator, tank and pump outdoors, with a remote control panel indoors.

Request a Quote

Outdoor Central Chiller Series Applications

Pad-mounted plants
Pad-mounted plants
Central chilled water
Central chilled water
Plant-wide molding
Plant-wide molding
Winter glycol loops
Winter glycol loops

schematic of the Outdoor Central Chiller series circuit, showing where the process fluid and the condenser heat go

Account for the Pump Derate

Mokon publishes the outdoor central capacities before the pump, and says to derate for the pump selected. A 7-1/2 hp pump puts its heat into the loop, and the chiller has to remove it along with the load. The figures on these pages are Mokon's as published; the derate is part of the confirmation before we quote.

Outdoors the loop sees winter whatever the process does, so the glycol type and mix guide applies here too.

Every part-number page below names the Temptek unit we supply in its place, a Temptek outdoor packaged chiller for the air-cooled models and a Temptek TTI water-cooled central chiller for the water-cooled ones, sized to cover the published capacity.
Call and talk it through with an engineer: 1-805-484-2992

Mokon Outdoor Central: Pump Derate and Tank Size

Yes, proportionally: the same 7-1/2 hp pump is a much larger share of an OAC-30's 356,000 Btu/h, about 29.7 tons, than of a 120-ton unit. Mokon lists 3, 5 and 7-1/2 hp as standard, and the heat each adds comes off the published capacity before the process sees any of it. A high-head pump chosen for a long run to the far end of the plant is the case to watch on the small sizes. Tell us which pump your unit carries, and the confirmation counts its heat against the load.

That an OAC-80 or larger has been giving the plant more than three times the stored fluid of a 60-ton unit, and the process may depend on it. Below 80 tons the tank is 100 or 150 gallons; at 80 and 100 tons it is 500, and at 120 it is 750. Check those volumes against the quoted unit's tank. If the new chiller carries less and the load swings, add a buffer tank so the compressors do not short-cycle and the leaving temperature holds.

They come out of service, because the Temptek units for the air-cooled OAC sizes are outdoor packaged chillers with the condenser on board. The OAC-60, listed at 724,000 Btu/h before the pump derate, is the first size Mokon supplies with a remote air-cooled condenser. Plan for removing the condenser and its refrigerant piping, recovering the charge, and setting the new chiller where it gets clean air. The pad must take the whole package in one place, so check its size and load rating before delivery.

Yes on paper: the OAC-80 is published at 74.17 tons against the TTOACS-80D-MZC-2P's 75.8, about 1.6 tons in hand, while the OAC-100 at 92.83 tons has 17.3 tons spare on the TTOACS-120D-MZC-2P's 110.1. Temptek rates both at 95°F ambient, five degrees above Mokon's 90°F. Mokon's figures are also before the pump derate, so the OAC was delivering a little less to the process then the table shows. On the water-cooled side the OWC models map to TTI water-cooled central chillers, such as the TTI-50W for the OWC-50 and the TTI-100W for the OWC-100.