Replacement unit for the Drake PWC Semi-Hermetic Series

PWC Semi-Hermetic Series

Semi-hermetic compressors on condenser water: Drake's PWC -S units, 10 to 100 hp, single or dual circuit, for colder process duty.

PRODUCT TYPE CAPACITY MODELS
Packaged Chiller Water-Cooled Packaged 10 to 100 HP 21

Specifications


Configuration & Size

Horsepower:
10 to 100 hp
Models:
21 part numbers
Capacity:
12.6 to 88.5 tons at 50°F
Circuits:
Single or dual
Refrigerant:
R407C, R404A

Construction

  • Semi-hermetic compressors
  • Single or dual circuit
  • Water-cooled condenser
  • Stainless brazed plate evaporator
  • NEMA 3R electrical

Ratings

  • Tables from 20 to 65°F leaving
  • 105°F condensing column used
  • R407C 10 to 55°F suction
  • R404A -10 to 45°F suction

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

PWC Semi-Hermetic Water-Cooled Chillers, 10 to 100 HP

Low-Temperature Capacity Indoors

Twenty-one models. Single-circuit PWC100S-S to PWC500S-S and dual-circuit PWC150D-S to PWC1000D-S units, each on semi-hermetic compressors with a water-cooled condenser.

Tables run from 20 to 65°F. The PWC100S-S sheet lists 6.3 tons at 20°F up to 16.9 tons at 65°F leaving fluid at 105°F condensing on R407C, and 4.1 to 13.7 tons from 0 to 55°F on R404A.

Wide suction ranges. Drake lists 10 to 55°F suction on R407C and -10 to 45°F on R404A for these units.

No tank on board. These are chiller-only packages, piped to a separate tank and pump.



campus chilled water plant with blue insulated headers and valves

Semi-hermetic compressors and water-cooled condensers for colder glycol, indoors.

Request a Quote

PWC Semi-Hermetic Series Applications

Low-temperature glycol
Low-temperature glycol
Cold storage
Cold storage
Tower-water plants
Tower-water plants
Food processing
Food processing

schematic of the PWC Semi-Hermetic series circuit, showing where the process fluid and the condenser heat go

Select at the Temperature You Run

A semi-hermetic water-cooled unit is usually running glycol in the 20s, where it makes well under half its warm-water capacity. The pages below match at 50°F, the point Temptek rates at, which is right for warm process water and too optimistic for a low-temperature process. For a colder set point we select at your temperature and glycol mix.

The glycol type and mix guide covers the glycol mix, and the leaving fluid temperature guide the capacity at each set point.

Every part-number page below names the Temptek unit we supply in its place, matched at 50°F leaving fluid and 105°F condensing: a Temptek CG water-cooled portable to 40 tons, and a TTI water-cooled central chiller above.
Call and talk it through with an engineer: 1-805-484-2992

Drake PWC -S Units: What to Know Before Sizing

Only at the warm end: a 50°F suction limit, against the usual 55°F, caps how warm a leaving fluid the sheet covers. Suction runs below the leaving fluid, so a process at 50°F or colder sits inside either limit. It can matter if a PWC1000D-S, one of those sheets, has been moved to warm process water in the 60s. Check its sheet before relying on the 88.5-ton figure for that duty.

A chiller that runs flat out and never reaches set point: the loop sits several degrees warm under load, recovers only overnight, and the compressors log long run hours with almost no cycling. That happens because the 50°F match overstates low-temperature capacity by about two to one. The PWC250S-S is published at 25 tons at 50°F but 11.5 tons at 20°F, and the PWC800D-S at 74.1 against 36.1 tons. In a cold storage or food plant, the first sign is often product temperatures creeping up through the day shift. For a process in the 20s, give us the set point and glycol mix and we select at that temperature.

Because the PWC500S-S is published at 44.3 tons on the 50°F row at 105°F condensing, above the 40-ton CG-40W, while the PWC400S-S, at 37.1 tons, still fits under it. The PWC400S-S therfore takes the CG-40W portable with 2.9 tons to spare, and the PWC500S-S takes the TTI-50W water-cooled central chiller at 50 tons. The same reasoning sends the PWC1000D-S, at 88.5 tons, to the TTI-90W. Every PWC -S is a chiller-only package feeding its own tank and pump elsewhere in the plant, so that station stays in the picture whichever format is chosen; send its pump flow and tank volume with the model.

No: most PWC -S sheets list a -10 to 45°F suction range on R404A with capacity from 0°F, but the PWC301S-S sheet shows 10 to 55°F suction on both refrigerants, and its R404A table starts at 25°F, at 18.7 tons. Read literally, that unit is not tabulated below 25°F even on R404A, which is a surprise if a plant bought it for colder work. It may be a sheet error or a different compressor choice. Either way, confirm the nameplate refrigerant and the set point the unit actually holds before relying on any match.