1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the G&D ForgeLine HT Series

ForgeLine HT Series

Compact, outdoor-rated and built for the plant floor: G&D's ForgeLine HT industrial chillers, 0.5 to 6.1 tons.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Air-Cooled Industrial 0.5 to 6.1 Tons 7

Specifications


Configuration & Size

Capacity:
0.5 to 6.1 Tons
Models:
7 part numbers
Compressor:
Scroll (0.5 t: reciprocating)
Cabinet:
82 to 111 cm wide
Refrigerant:
R-513A

Construction

  • Scroll compressors (reciprocating on the 0.5 t)
  • Stainless steel plate evaporator
  • Outdoor-rated, corrosion-resistant chassis
  • Axial fans with step control
  • Evaporator inlet strainer

Ratings

  • 0.5 to 6.1 tons (brochure)
  • Rating temperature not stated
  • Refrigerant R-513A
  • Electrical not published

Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

ForgeLine HT Industrial Chillers, 0.5 to 6.1 Tons

Small Chillers for Hard Duty

Seven models, all air-cooled. G&D describes the ForgeLine as its rugged, air-cooled line for demanding manufacturing, processing and high-temperature applications. The GD-0005TFLN runs a reciprocating compressor and is for indoor use only; the six larger models run scroll compressors in an outdoor-rated, corrosion-resistant chassis.

Capacity runs from 0.5 to 6.1 tons, 1.8 to 21.5 kW, on R-513A, as listed in G&D's ForgeLine brochure. The brochure does not say at what leaving-fluid temperature or ambient those figures are rated, so treat them as nominal until the setpoint is confirmed.

Two cabinet sizes cover the range. The three smallest units sit in cabinets 82 to 88 cm wide; the four TFLR units share one 111 x 90 x 145 cm frame from 2.3 to 6.1 tons, which makes a later upsizing a like-for-like swap on the pad.

The published data stops there. G&D lists no electrical figures, pump, flow, tank, connection sizes or weights for the ForgeLine line. Those pages show what is published and nothing else; the nameplate fills the gaps.



glycol tank and chiller cabinet beside stainless fermenters

Scroll compressors, a stainless plate evaporator and an outdoor-rated chassis in a small footprint.

Request a Quote

ForgeLine HT Series Applications

Machine tool coolant
Machine tool coolant
High-temperature processes
High-temperature processes
Outdoor installation
Outdoor installation
Manufacturing and finishing
Manufacturing and finishing

schematic of the ForgeLine HT series circuit, showing where the process fluid and the condenser heat go

Outside, Next to the Machine

A ForgeLine unit is small enough to sit beside the building wall next to the machine it serves, with its condenser air on the outside and only the chilled fluid coming in. Axial fans with step control follow the load and the weather, and an inlet strainer ahead of the evaporator keeps shop debris out of the plate pack. The smallest model is the exception: it is rated for indoor use only.

Because G&D does not publish the rating temperture, check the setpoint before trusting the tonnage. A 2.3-ton figure at a 50°F water rating would be well under 2 tons on 30°F glycol. The leaving fluid temperature guide shows how quickly capacity falls with setpoint.

Each part-number page below names the Temptek unit we supply in its place, sized on the brochure tonnage: a CF fractional-ton portable for the three smallest, a CG portable to 4 tons, and a Temptek outdoor packaged unit for the GD-0061TFLR.
Call and talk it through with an engineer: 1-805-484-2992

ForgeLine HT: Ratings, Siting and the Temptek Match

Cooling. The brochure pairs 0.5 tons with 1.8 kW and 6.1 tons with 21.5 kW, about 3.5 kW per ton, which is the cooling conversion, not an electrical rating. Reading 21.5 kW as input power and sizing a breaker from it is the mistake to avoid, since G&D lists no voltage, amps or phase for the line at all. Take the electrical data from the nameplate of the unit in service, and send it with the leaving-fluid setpoint, because the tonnage itself carries no stated rating temperature.

None on paper: we supply the Temptek CG-3A, at 2.9 tons, for both the 2.3 and 2.9-ton TFLR models, so the larger one is matched ton for ton. The ForgeLine figure has no rating temperature, and if it was taken warmer than the Temptek rating, the CG-3A may in fact carry more; if colder, less. That is why the setpoint matters most on this model. The 3.4-ton TFLR maps to the CG-4A, the three smallest to a CF fractional-ton unit, and the GD-0061TFLR to the outdoor TTOACS-7.5S-CG-1P, at 7.8 tons on Temptek's 50°F rating, about 28 percent over its brochure figure. The CG and CF picks are indoor portables, so a unit that stood against an outside wall has to move inside.

Voltage, phase and full load amps first, then any rating point printed on it, because the published ForgeLine data covers none of them. Then note whether a tank and pump are on board, the flow the machine takes, the connection size, the setpoint and the fluid. The 3.4-ton TFLR model on a warm machine-coolant loop and the same unit holding 30°F glycol call for different selections, and the brochure tonnage alone cannot tell them apart.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales