Multi Stage Series

Two compressors on two circuits, staged to the load: G&D's mid-size glycol chillers, 10 to 27 HP.

PRODUCT TYPE CAPACITY MODELS
Glycol Chiller Outdoor Packaged 8.4 to 19 Tons 4

Specifications


Configuration & Size

Capacity:
8.4 to 19 Tons at 40°F
Models:
4 part numbers
Compressor:
Two per unit
Process Flow:
40 to 150 GPM
Refrigerant:
R-448A

Construction

  • Two complete refrigeration circuits
  • Brazed-plate evaporator, stainless plates
  • Insulated stainless reservoir with level indicator
  • Separate chiller pump on the larger units
  • Phase and voltage monitoring

Ratings

  • Rated at 20, 30 and 40°F glycol
  • 90°F ambient
  • Refrigerant R-448A
  • Power: 230/1 (smallest), 208-240/3, 460-480/3

Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

Multi Stage Glycol Chillers, 10 to 27 HP

Two Circuits for a Load That Moves

Four models, each with two complete refrigeration circuits. The GD-5x5H and GD-7x7H pair two 5 or 7 HP compressors; the GD-20H and GD-27H pair two 10 or 13.5 HP compressors. Each circuit is wired separately so the compressors can share run hours and stage on as the load climbs.

Capacity at 40°F runs 101,200 to 230,000 Btu/h, about 8.4 to 19 tons, in a 90°F ambient, on R-448A. At 20°F the range is 65,400 to 157,000 Btu/h.

The tank and pumps grow a step. The two smaller units carry a 115-gallon reservoir and 40 to 65 GPM of glycol flow; the GD-20H and GD-27H carry 230 gallons, a 5 HP process pump, a separate chiller pump and 150 GPM.

Staging is the reason to buy one. A brewery load swings from a steady fermentation hold to a crash-cool spike. Two compressors follow that swing better than one large one cycling, and if one circuit fails the other keeps the cellar cold.



outdoor glycol chiller with piping on a concrete pad beside a building

Two compressors, two circuits, one tank: redundancy for a cellar that cannot afford a warm night.

Request a Quote

Multi Stage Series Applications

Brewery fermentation
Brewery fermentation
Redundant cooling
Redundant cooling
Dairy and food tanks
Dairy and food tanks
Distillery condensers
Distillery condensers

schematic of the Multi Stage series circuit, showing where the process fluid and the condenser heat go

Two Circuits Feeding One Tank

Both circuits chill the same reservoir, and the glycol pump sends one loop to the process. The controller brings the second compressor on only when the first cannot hold the setpoint, so most of the year one circuit runs and the other waits.

That makes the two-circuit unit a partial backup, not a full one. With one compressor down a GD-20H makes roughly half its rated capacity; enough to hold a cellar at temperature, rarely enough to crash-cool on schedule. If the process cannot tolerate that, size so that one circuit carries the essential load.

Each part-number page below names the Temptek unit we supply in its place. Each is sized to cover the G&D unit at 20°F, and the two larger sizes map to a dual-zone Temptek outdoor unit, which keeps the two-circuit redundancy.
Call and talk it through with an engineer: 1-805-484-2992

Two-Circuit Questions: G&D Multi Stage

Halve the 20°F figure and check it against the steady load with every crash finished. A GD-20H at 128,000 Btu/h gives about 5.3 tons per circuit, so it can hold a cellar whose fermentation load is under about 5 tons with one compressor down. A GD-5x5H, at 65,400 Btu/h, leaves about 2.7 tons on one circuit. If the hold load is 4 tons, the GD-5x5H is the wrong pick even though its two circuits together cover the load, and the GD-27H, rated 157,000 Btu/h at 20°F, gives about 6.5 tons per circuit for a cellar that has grown. Remember the crash that was running when the compressor failed: it will not finish on one circuit, so the plan also needs a decision about which tanks wait. Work out the hold seperately from the crash, size each circuit to the first and the pair to the second.

About 60 percent more current than three-phase at the same 230 V: G&D lists 84 full load amps on single-phase, 53 on 230 V three-phase and 28 on 460 V. It is the only Multi Stage size listed on single-phase at all. An 84-amp chiller is a large load for a small brewery service, and it often decides whether a utility upgrade is needed before the cellar opens. The GD-7x7H runs three-phase on 230 V or 460 V, and the two larger models on 208-240 V or 460-480 V, so outgrowing the GD-5x5H also means three-phase power.

Steady flow through the evaporator, whatever the jacket valves are doing. On these two sizes a 1.5 HP chiller pump circulates the reservoir through the brazed-plate evaporator while the 5 HP process pump serves the tanks. The GD-5x5H and GD-7x7H do both jobs with one glycol pump, so when most jackets are satisfied and their valves close, evaporator flow falls with them. Low flow through a brazed plate at glycol temperatures is how evaporators freeze. On the smaller units, keep a bypass path open so the pump always has somewhere to send glycol.

Yes on both counts, though the margin is thin. We supply the Temptek TTOACS-30D-MZC-2P, a dual-zone outdoor unit rated 27.7 tons at 50°F, which is about 11.1 tons at 20°F on Temptek's published 0.40 multiplier, roughly 4 percent over the 10.7 tons G&D publishes for the GD-20H there. Its two zones carry over the two-circuit fallback. The small margin is fine where the GD-20H has been keeping up; if it struggled on summer crashes, or tanks have been added since, the next size up is the safer choice. The GD-27H maps to the TTOACS-40D-MZC-2P, and the GD-5x5H and GD-7x7H to single-zone TTOACS-15S-CG-1P and TTOACS-20S-CG-1P units.

About 2.4 more tons at 20°F, with the same tank and pumps. G&D publishes the GD-27H at 157,000 Btu/h at 20°F, about 13.1 tons, against 10.7 for the GD-20H, and at 40°F the gap is 19.2 against 16.3 tons. Both carry 230 gallons and identical pumping, so the step buys compressor capacity only. That suits a cellar that has outgrown its crash schedule but not its header.


Multi Stage Units


Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales