1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the G&D Scroll Series

Scroll Series

Tandem scroll compressors, a stainless tank and a process pump on one outdoor frame: G&D's large packaged process chillers, 20 to 200 nominal tons.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Outdoor Packaged 20 to 200 Tons 11

Specifications


Configuration & Size

Capacity:
20 to 200 Tons nominal
Models:
11 part numbers
Compressor:
Tandem scroll
Process Flow:
65 to 500 GPM
Refrigerant:
R-410A

Construction

  • Tandem scroll compressor pairs
  • Air-cooled condenser, outdoor frame
  • Stainless reservoir with level indicator
  • CTS flange supply and return
  • Microprocessor controls with comms

Ratings

  • Rated at 30 to 60°F (published units)
  • 90°F ambient
  • Refrigerant R-410A
  • Power: 460-480/3 (published units)

Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

Scroll Process Chillers, 20 to 200 Tons

Tandem Scrolls for Medium-Temperature Plant Loads

Eleven models on tandem scroll compressors. The 20 to 65-ton units carry one tandem pair, the 80-ton and up two pairs or more, each unit a complete outdoor package with a stainless reservoir and a process pump.

The numbers are nominal tons, and G&D rates the line for medium-temperature work: the GD-120T-4HE is published at 1,254,000 to 1,771,000 Btu/h across 40 to 60°F, and the GD-140T-4 at 1,290,000 to 1,830,000 Btu/h across 30 to 50°F, in a 90°F ambient, on R-410A.

The published product-page figures cover the whole line: tanks from 190 to 2,000 gallons, process pumps of 2 to 15 HP and 65 to 500 GPM at 25 PSI, and connections from 2 to 6 inches.

Most of the spec sheets cannot be read. G&D publishes the 20 to 100-ton sheets as outlined artwork, and the GD-200T-6 page links the GD-120T-4HE sheet. Those pages show the product-page figures only.



three modular chiller units side by side in an industrial plant

Tandem scroll pairs on an outdoor frame, with the tank and the process pump in the package.

Request a Quote

Scroll Series Applications

Distilleries
Distilleries
Solvent recovery
Solvent recovery
Chemical process loops
Chemical process loops
Plastics and molding
Plastics and molding

schematic of the Scroll series circuit, showing where the process fluid and the condenser heat go

Staging on Scroll Pairs

A tandem pair is two scroll compressors piped in parallel on one circuit. At part load one runs; at full load both do. On the larger units two or three pairs give four or six steps of capacity, which lets the plant follow a varying load without the long off-cycles that let the tank temperature drift.

G&D describes the line as suited to distilleries, solvent recovery and general industrial loads, all duties that run in the 40s and 50s. G&D also sells the same model numbers from 20 to 100 tons as its comfort-cooling HVAC line; the pages here are the process units.

Each part-number page below names the Temptek dual-zone outdoor chiller we supply in its place, sized from the coldest published capacity or from the nominal tonnage where the sheet cannot be read. The GD-200T-6 is beyond the largest Temptek unit, and its page points to our sister site's largest outdoor units.
Call and talk it through with an engineer: 1-805-484-2992

G&D Scroll Series, 20 to 200 Tons: Buyer Questions

No, it makes about 107 tons there: G&D publishes 1,290,000 Btu/h at 30°F in a 90°F ambient, rising to 1,830,000, about 152 tons, at 50°F. The nominal 140 therefore sits somewhere in the 40s. A plant running a 30°F glycol header that buys on the model number is short by more than 30 tons before the first hot afternoon. The GD-120T-4HE shows the same spread at warmer points, from about 104 tons at 40°F to 148 at 60°F. For a true 140-ton load at 30°F, the published figures point to a larger unit or a pair, and the header pump has to carry the flow for the full load, not the nominal. Size from the published figure at the setpoint, or from a measured load taken across the header with supply and return temperatures and flow recorded together.

Often not, and it should be checked before flow. The product pages rate every process pump at 25 PSI, from 2 HP and 65 GPM on the GD-20T-2 to 15 HP and 500 GPM on the GD-200T-6. On the water formula those flows carry about 27 and 208 tons at a 10°F rise, so flow is matched to the tonnage; the pressure is what runs out on a header that crosses a large building to condensers, jacketed vessels and control valves. Add up the pressure drop on the longest path at design flow. If it exceeds 25 PSI, plan a booster pump or a larger process pump in the selection.

Look for the stainless reservoir and process pump in the package: the process units carry both, from a 190-gallon tank on the GD-20T-2 up. G&D uses identical model numbers between 20 and 100 tons for its comfort-cooling line, and only the process units are listed here. Photograph the frame and nameplate together; if there is no tank on board, tell us, since the quote then has to cover pumping and storage separately.

Our sister line's outdoor air-cooled central chillers, which reach 210 tons, used in pairs when the load is above one unit. The GD-200T-6 carries a 2,000-gallon tank and a 15 HP pump at 500 GPM, and its page links the GD-120T-4HE sheet, so no capacity of its own is published; size it from a measured load or the nameplate. Below it, the GD-120T-4HE maps to the Temptek TTOACS-150D-MZC-2P, about 116.6 tons at 40°F against G&D's 104.5, and the GD-100T-4 to the TTOACS-120D-MZC-2P at 110.1 tons at 50°F, chosen on nominal tonnage.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales