One 168 x 98 x 94-inch footprint, four independent refrigeration circuits, and a 400-gallon tank, configured from 40 to 100 hp.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Glycol Chiller | Four-Circuit Packaged | 40 to 100 HP | 5 |
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.
Five configurations. The 4B410E400V at 40 hp to the 4B425E400V at 100 hp share one frame, a 400-gallon tank, a 210 GPM pump at 84 ft and 3-inch MNPT connections.
Rated two ways. PRO publishes R449A and R454C at 80°F and 90°F ambient: on R449A at 90°F, 339,600 to 744,800 Btu/h at 30°F leaving glycol.
Four independent circuits. With independent heat exchangers for cooling and heating, and circuits PRO describes as upgradeable as refrigerant rules change.
Heavy and loud. From 10,400 to 11,200 lbs operating, 44,000 CFM of condenser air and 82 dB.
Four independent refrigeration circuits, a 400-gallon tank and one pump in a single packaged frame.
Request a Quote
The PRO4 table shows what the refrigerant does: the 60 hp unit makes 467,600 Btu/h at 30°F on R449A and 426,800 on R454C, both at 90°F ambient. Ask which one the nameplate carries before comparing. Four circuits also mean a trip takes out a quarter, not half.
Every part-number page below names the Temptek unit we supply in its place, sized from PRO's 30°F figure on Temptek's published multiplier: a Temptek unit makes 0.60 of its 50°F rating at a 30°F set point, so the pick is the PRO figure divided by 0.60. The R449A figure is used.
Call and talk it through with an engineer: 1-805-484-2992