Replacement unit for the PRO Refrigeration PRO4 Series

PRO4 Series

One 168 x 98 x 94-inch footprint, four independent refrigeration circuits, and a 400-gallon tank, configured from 40 to 100 hp.

PRODUCT TYPE CAPACITY MODELS
Glycol Chiller Four-Circuit Packaged 40 to 100 HP 5

Specifications


Configuration & Size

Capacity:
339,600 to 744,800 Btu/h at 30°F
Models:
5 part numbers
Horsepower:
40 to 100 hp
Pump:
210 GPM at 84 ft
Tank:
400 gallons

Construction

  • Five compressor options, mix and match
  • Four independent circuits
  • Independent heat exchangers
  • 400-gallon glycol tank
  • PROElliot monitoring

Ratings

  • Rated at 20 to 35°F glycol
  • 80°F and 90°F ambient
  • R449A or R454C
  • 208, 230 or 460 V

Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.

PRO4 Series, 40 to 100 HP

Four Circuits in One Frame

Five configurations. The 4B410E400V at 40 hp to the 4B425E400V at 100 hp share one frame, a 400-gallon tank, a 210 GPM pump at 84 ft and 3-inch MNPT connections.

Rated two ways. PRO publishes R449A and R454C at 80°F and 90°F ambient: on R449A at 90°F, 339,600 to 744,800 Btu/h at 30°F leaving glycol.

Four independent circuits. With independent heat exchangers for cooling and heating, and circuits PRO describes as upgradeable as refrigerant rules change.

Heavy and loud. From 10,400 to 11,200 lbs operating, 44,000 CFM of condenser air and 82 dB.



refrigerant receiver tanks in a machine room

Four independent refrigeration circuits, a 400-gallon tank and one pump in a single packaged frame.

Request a Quote

PRO4 Series Applications

Brewery fermentation
Brewery fermentation
Dairy plants
Dairy plants
Redundant circuits
Redundant circuits
Outdoor pads
Outdoor pads

schematic of the PRO4 series circuit, showing where the process fluid and the condenser heat go

R449A or R454C Changes the Number

The PRO4 table shows what the refrigerant does: the 60 hp unit makes 467,600 Btu/h at 30°F on R449A and 426,800 on R454C, both at 90°F ambient. Ask which one the nameplate carries before comparing. Four circuits also mean a trip takes out a quarter, not half.

Every part-number page below names the Temptek unit we supply in its place, sized from PRO's 30°F figure on Temptek's published multiplier: a Temptek unit makes 0.60 of its 50°F rating at a 30°F set point, so the pick is the PRO figure divided by 0.60. The R449A figure is used.
Call and talk it through with an engineer: 1-805-484-2992

Four-Circuit PRO4: Questions Before a Changeout

Nothing carries over unless it is written into the selection, because the Temptek unit is matched on tons rather than on circuit count. On a PRO4 each of the four circuits has its own heat exchanger, so a single trip costs about a quarter of capacity: on the 100 hp unit, roughly 186,000 of its 744,800 Btu/h at 30°F. Many plants have never noticed a PRO4 circuit fault because the other three carried the load. A replacement may stage differently, and a loss that once went unseen can become a warm fermenter. If the plant cannot run on three-quarters capacity for a day, say so, and the redundancy is built into the layout instead of being left to the model match.

Temptek's 55.1-ton rating is at 50°F, while the PRO4's 28.3 tons is at 30°F glycol, so the two figures are not on the same footing. The 40 hp 4B410E400V makes 339,600 Btu/h at 30°F on R449A in a 90°F ambient. Divided by 0.60, that needs 47.17 tons of 50°F rating, and the TTOACS-60S-CG-1P at 55.1 tons is the size that clears it; at 30°F it makes about 33 tons, under five tons above the PRO4, not double. The same reading applies at the top: the 100 hp 4B425E400V, at 62.07 tons, needs 103.4 tons, covered by the 110.1-ton TTOACS-120D-MZC-2P, which is about 66 tons at 30°F. Between them, the 60 hp takes the TTOACS-80D-MZC-2P and the 80 hp the TTOACS-100D-MZC-2P. A PRO4 whose nameplate shows R454C made less than these R449A figures, so its pick carries extra margin.

It tells you the loop's supply-to-return spread depends on the configuration, because every PRO4 size uses the same 210 GPM pump at 84 ft. On a water basis, 210 GPM carries the 40 hp unit's 339,600 Btu/h across about 3.2°F and the 100 hp unit's 744,800 Btu/h across about 7.1°F. With glycol in the loop instead of water, both spreads run slightly wider in practice. The common error is copying 210 GPM onto the new unit without checking whether the loop actually passes it; throttled valves and added jackets often mean it does not. Measure the real flow and the supply and return temperatures, and the replacement pump is chosen from those and from the 3-inch MNPT connections it has to meet.

It means the pad's clearances were laid out for one airflow pattern, and the replacement's may differ. The PRO4 moves 44,000 CFM at 82 dB from a 168 x 98 x 94-inch frame. Where the pad sits against a building, a fence or another unit, warm discharge air finding it's way back to the intake raises the effective ambient, and capacity falls with it. Plants that never saw this on the PRO4 can see it after a swap if the new unit discharges in a different direction. Send a sketch of the pad with the walls and equipment around it, plus the 460 V feeder size, since the PRO4 runs from 118 A MCA on the 40 hp to 221 A on the 100 hp, so placement and power are checked together.